Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

239

5

Motor control (MCTRL)

5.12

Monitoring

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.12.2

Motor overload monitoring (I2xt)

The Inverter Drives 8400 are provided with a simple, sensorless, thermal I

2

xt motor monitoring of

self-ventilated standard motors which is based on a mathematical model.

C00066

displays the calculated motor load in [%].

• If the calculated motor load reaches the motor load setting (

C00120

):

• The error response set in

C00606

will be carried out (Lenze setting: "Warning").

• The "

oC6: I2xt motor overload

" error message will be entered into the Logbook.

• The bMctrlI2xtOverload status output of the

LS_DeviceMonitor

system block will be set to

TRUE.

• A setting of

C00606

= "0: No Reaction" deactivates the monitoring.

Stop!

I

2

xt motor monitoring does not provide full motor protection!

As the motor utilisation calculated in the thermal motor model is lost after mains

switching, for instance the following operating states cannot be detected correctly:

• Restarting (after mains switching) of a motor that is already very hot.
• Change of the cooling conditions (e.g. cooling air flow interrupted or too warm).

A full motor protection requires additional measures as e.g. the evaluation of

temperature sensors that are located directly in the winding or the use of thermal

contacts.
For the installation according to UL or UR, the safety instructions provided in the

hardware manual must be observed! Among other things, the activation of the motor

overload monitoring (I2xt) is required here.

Note!

From version 12.00.00

, the thermal motor load displayed in

C00066

can be pre-

initialised when the device is connected to the mains, optionally using a fixed value or

the value used last at the time when the device was switched off. The desired

initialisation is selected in

C00122

. In the Lenze setting of

C00122

, the behaviour

remains unchanged (no initialisation).