11 braking operation/brake energy management, Braking operation/brake energy management, 5motor control (mctrl) – Lenze 8400 StateLine User Manual

Page 226

Advertising
background image

5

Motor control (MCTRL)

5.11

Braking operation/brake energy management

226

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.11

Braking operation/brake energy management

When braking electrical motors, the kinetic energy of the drive train is fed back regeneratively to the

DC bus. This energy results in a boost of the DC-bus voltage.

• Several different strategies can serve to avoid DC-bus overvoltages:

• Use of a brake resistor
• Stopping of the ramp function generator if brake chopper threshold exceeded (RFG_Stop)
• Use of the "inverter motor brake" function

(from version 04.00.00)

• Combination of the above named options

• In the case of inverters with a 3-phase supply, the following is also possible:

• Coupling of the inverters in a DC-bus connection
• Recovery of regenerative energy with a regenerative module

Stop!

If the connected brake resistor is smaller than required, the brake chopper can be

destroyed!

• Appropriate protective measures are described in subchapter "

Avoiding thermal

overload of the brake resistor

".

( 234)

If no brake resistor or regenerative module is used, the overvoltage switch-off ("

oU

") may

respond, e.g. in case of short deceleration times during feedback operation.

Error

messages of the operating system

( 444)

Advertising