C00173 | mains voltage, C00174 | reduc. brake chopper threshold, C00175 | brake energy management – Lenze 8400 StateLine User Manual

Page 642: C00173, C00175, C00174, Threshold, Selected in, Voltage, Ans of

Advertising
background image

15

Parameter reference

15.2

Parameter list | C00173

642

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00173

C00174

C00175

Parameter | Name:

C00173 | Mains voltage

Data type: UNSIGNED_8

Index: 24402

d

= 5F52

h

If the rated mains voltage differs from 230 V or 400 V, set the mains voltage the drive is operated with.

The set mains voltage influences the brake chopper threshold, the monitoring of the device utilisation (Ixt) and the

switch-off threshold in case of undervoltage in the DC bus.
Selection list

(Lenze setting printed in bold)

Info

0 3ph 400V / 1ph 230V

3-phase 400 V or 1-phase 230 V

1 3ph 440V / 1ph 230V

3-phase 440 V or 1-phase 230 V

2 3ph 480V / 1ph 230V

3-phase 480 V or 1-phase 230 V

3 3ph 500V / 1ph 230V

3-phase 500 V or 1-phase 230 V

4 Reserved / reserved

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00174 | Reduc. brake chopper threshold

Data type: UNSIGNED_8

Index: 24401

d

= 5F51

h

The threshold from which on the brake chopper is controlled is reduced by the voltage value set here.
Setting range

(min. value | unit | max. value)

Lenze setting

0

V

150 0 V

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00175 | Brake energy management

Data type: UNSIGNED_8

Index: 24400

d

= 5F50

h

From version 03.00.00

Selection of the braking procedure

Select response if the brake resistor is controlled

Selection list

(Lenze setting printed in bold)

Info

0 R_Brems

The brake resistor is used. When the threshold voltage

(

C00174

) is exceeded, the brake resistor is energised.

1 RfgStop

The "Ramp function generator stop" signal

(MCTRL_bRfgStop) is used. When the threshold voltage is

exceeded (

C00174

), the ramp function generator is

stopped.

2 R_Brems + HlgStop

The brake resistor and the "Ramp function generator

stop" signal are used. When the threshold voltage is

exceeded (

C00174

), the brake resistor is energised and

the ramp function generator is stopped.

3 FI_MotBrk + RfgStop

From version 04.00.00

Braking is performed by a superimposed speed setpoint

vibration in conjunction with "Ramp function generator

stop".

4 R_Brems + FU_MotBrk + HlgStop

From version 04.00.00

Braking is performed by combining all three braking

procedures.

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1