Warning, Ps01: no, Memory module – Lenze 8400 StateLine User Manual

Page 464: Xx.0135.00003, Xx.0140.00013, Xx.0135.00004, Xx.0144.00001, 9diagnostics & error management

Advertising
background image

9

Diagnostics & error management

9.9

Error messages of the operating system

464

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

CE3: CAN RPDO3 [xx.0135.00003]

CE5: CAN RPDO4 [xx.0135.00004]

CI01: Module missing/incompatible [xx.0140.00013]

PS01: No memory module [xx.0144.00001]

Response (Lenze setting printed in bold)

Setting:

C00593/3

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

CAN on board

: Time monitoring for RPDO3 has been

triggered.

• RPDO3 has not been received within the monitoring

time set in

C00357/3

or was faulty.

• Set correct telegram length for CAN master

(transmitter).

• Eliminate electrical interference (e.g. EMC).

• Adjust monitoring time

C00357/3

or switch off time

monitoring.

Response (Lenze setting printed in bold)

Setting:

C00593/4

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

CAN on board

: Time monitoring for RPDO4 has been

triggered.

• RPDO4 has not been received within the monitoring

time set in

C00357/4

or was faulty.

• Set correct telegram length for CAN master

(transmitter).

• Eliminate electrical interference (e.g. EMC).

• Adjust monitoring time

C00357/4

or switch off time

monitoring.

Response (Lenze setting printed in bold)

Setting:

C01501/2

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The optional communication module has been removed

or there is a connection problem or incompatibility with

the standard device.

• Check connection between the communication

module and standard device.

• Check if the module is plugged in correctly.

• In case of an incompatibility, either the module or the

software of the standard device is out of date. In this

case, please contact Lenze.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Memory module is either not available or not snapped

into place correctly.

• If a memory module has been provided: Plug the

memory module into the slot of the standard device

intended for this purpose.

• If a memory module has been provided: Check if the

memory module has been plugged-in correctly.

Advertising