4 optimising the control mode, Optimising the control mode, Chapter – Lenze 8400 StateLine User Manual

Page 185: 5motor control (mctrl)

Advertising
background image

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

185

5

Motor control (MCTRL)

5.8

Sensorless control for synchronous motors (SLPSM)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.8.4

Optimising the control mode

The measures described in the following subchapters serve to further optimise the control

behaviour of the sensorless control for synchronous motors and adjust it to the concrete

application.

Optimise current controller

.

( 186)

• The current controller should always be optimised if a motor of a third-party manufacturer

with unknown motor data is used!

Optimise speed controller

.

( 187)

• The setting of the speed controller must be adapted depending on the mechanical path.

Optimise response to setpoint changes and determine mass inertia

.

( 190)

• For an optimal reference behaviour, the total moment of inertia can be used to make a

feedforward control of the speed setpoint.

Current-dependent stator leakage inductance Ppp(I)

.

( 193)

• If the motor is operated with very low and very high currents during the process (e.g. in Pick

and place-applications), the stator leakage inductance and current controller parameters can

be tracked by means of an adjustable saturation characteristic.

Note!

From version 12.00.00:

• Following successful motor parameter identification, the current controller

parameters (

C00075

,

C00076

) are calculated automatically.

• If these parameters are not to be calculated, bit 4 of

C02865/1

must be set to "1".

• Following successful motor parameter identification, the speed controller parameters

(

C00070/3

,

C00071/3

) can be calculated automatically.

• If these parameters are to be calculated, bit 6 of

C02865/1

must be set to "5".

• Following successful motor parameter identification, other controller parameters

(

C00011

,

C00022

) can be calculated automatically.

• If these parameters are to be calculated, bit 6 of

C02865/1

must be set to "6".

Note!

Current setpoint filter (band-stop filter) / jerk limitation
The use of the functions is only recommended in exceptional cases.

Setting the current setpoint filter (band-stop filter)

( 195)

Adapting the max. acceleration change (jerk limitation)

( 196)

Advertising