C02865

Subcodes

Lenze setting

Info

C02864/1

0x0000

MCTRL

: Optimisations

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Parameter | Name:

C02864 | MCTRL: Optimisiations

Data type: UNSIGNED_16

Index: 21711

d

= 54CF

h

Parameter | Name:

C02865 | MCTRL: Special settings

Data type: UNSIGNED_16

Index: 21710

d

= 54CE

h

From version 12.00.00

Activation of special functions of the internal motor control
Setting range

(min. hex value | max. hex value)

0x0000

0xFFFF

Value is bit-coded:

Info

Bit 0 No TorqueLimit if TorquemodeOn

From version 12.00.00 onwards

: If sensorless vector

control (

SLVC

) is used, in the "torque control with speed

limitation", mode the torque limitation via

nTorqueMotLimit_a and nTorqueGenLimit_a is also

active to limit the torque setpoint.

If you want to deactivate the torque limitation to retain

the former function, set bit 0 to "1".

0 ≡ Torque limitation is active

1 ≡ Torque limitation is not active

Bit 1 250ms IMP before DCB
Bit 2 1000ms IMP before DCB
Bit 3 DCB: Current controller and C036

app. to C088

Bit 4 Motorident.: No calculation C73 C75

C76 C77 C78

From version 12.00.00 onwards

: Following successful

motor parameter identification, the current controller

and field controller parameters are calculated as well.

If these parameters are not to be calculated, bit 4 must

be set to "1".

0 ≡ Calculate parameter

1 ≡ Do not calculate parameter

Automatic motor data identification

Bit 5 Motorident.: Calculation C70 C71

C72

From version 12.00.00 onwards

: Following successful

motor parameter identification, the speed controller

parameters can automatically be calculated as well.

If these parameters are to be calculated, bit 5 must be set

to "1".

0 ≡ Do not calculate parameter

1 ≡ Calculate parameter

Automatic motor data identification

Bit 6 Motorident.: Calculation C11 C22

C497 C966 C982

From version 12.00.00 onwards

: Following successful

motor parameter identification, further controller

parameters can be calculated automatically.

If these parameters are to be calculated, bit 6 must be set

to "1".

0 ≡ Do not calculate parameter

1 ≡ Calculate parameter

Automatic motor data identification

Bit 7 Brake chopper off in case of pulse

inhibit

From version 14.00.00

0 ≡ No response of the brake chopper in case of pulse

inhibit.

1 ≡ In case of pulse inhibit, the brake chopper is

permanently switched off without any delay.

Braking operation/brake energy management