Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

283

6

I/O terminals

6.2

Analog terminals

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Using current input A1I
In the Lenze setting, voltage signals in the range of ± 10 V are evaluated via the A1U input terminal.

If current signals are detected via the A1I input terminal instead, the selection "1: 0...20mA" or

"2: 4...20mA" is to be set in

C00034

.

Tip!
By selecting "2: 4...20mA", you can implement a 4 ...20 mA current loop, e.g. for stipulation

of the speed setpoint.

Open-circuit monitoring
In the case of configuration as a 4 ... 20 mA current loop, the fault response set in

C00598

takes place

in the event of a wire breakage (Lenze setting: "TroubleQuickStop").