Oh3: motor temperature (x106) triggered, Error m, Sible temperature. the – Lenze 8400 StateLine User Manual

Page 454: Oh1: overtemperature, Heatsink, Oh4: heatsink, Temp.. > switch-off temp °c, Xx.0119.00001, Xx.0119.00015, Xx.0119.00000

Advertising
background image

9

Diagnostics & error management

9.9

Error messages of the operating system

454

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Su04: CU insufficiently supplied [xx.0111.00004]

Su06: Mains input overload [xx.0111.00006]

oH4: Heatsink temp. > shutdown temp. -5°C [xx.0119.00000]

oH1: Heatsink overtemperature [xx.0119.00001]

oH3: Motor temperature (X106) triggered [xx.0119.00015]

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

After switching on the device, the 24V supply voltage for

the control electronics is too low (100 ms after switch-on

U is < 19V).

• The current supply voltage is displayed in

C00065

.

With internal supply voltage via the power electronics,

the controller must be replaced.

With external supply voltage, check the correct

connection and/or the stability of the supply voltage.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

In order to protect the device from overload, the

following device outputs have a hardware detection in

the mains input: 7.5 kW, 11 kW, 15 kW, 30 kW, 37 kW, 45

kW.

In case of the error message "Su06", this hardware

detection has responded.

• Check whether all mains phases are connected (a 2-

phase supply may be existent).

• Provide for sufficient cooling of the device.

Response (Lenze setting printed in bold)

Setting:

C00582

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The heatsink temperature now only differs by 5 °C from

the shutdown temperature of the motor.

Prevent further heating, i.e. reduce motor load or set

controller inhibit so that the heatsink can cool down

again.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The heatsink temperature is higher than the fixed limit

temperature (90 ° C).

Maybe the ambient temperature of the controller is too

high or the fan or its ventilation slots are dirty.

• Check control cabinet temperature.

• Clean filter.

• Clean controller.

• If required, clean or replace the fan.

• Provide for sufficient cooling of the device.

Response (Lenze setting printed in bold)

Setting:

C00585

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The motor temperature monitoring function at the plug

connector X106, terminal T1 /T2, has tripped.

Possible causes:

• The motor is overheated so that the thermal contact

integrated into the motor has been switched.

• An open circuit or a loose contact at the connections

mentioned above has occurred.

• Check motor temperature monitoring.

• Provide for sufficient cooling of the motor.

• Check terminals for open circuit or loose contact.