Parameter change-over

14.1

Configuring parameter change-over via the »Engineer« parameterisation dialog

582

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

14.1.2

Configuring control inputs

The three control inputs for parameter change-over can be configured via the following parameters:

Truth table for the selection of the value set to be used:

Parameter

Lenze setting

Info

Activate writing

(

C00621/123

)

0: Not connected

Selection of the signal source that activates writing

to the parameter list (for

Execute Mode

= "0: by

Execute").

Selection value set - 1

(

C00621/124

)

0: Not connected

Selection of the two signal sources for the binary-

coded selection of the value set 1 ... 4 to be used (see

following truth table).

Selection value set - 2

(

C00621/125

)

0: Not connected

Selection value set - 1

Selection value set - 2

Value set used

FALSE

FALSE

Value set 1

TRUE

FALSE

Value set 2

FALSE

TRUE

Value set 3

TRUE

TRUE

Value set 4