C00975 | vfc-eco: vp cosphi controller, C00976 | vfc-eco: ti cosphi controller, C00977 | vfc-eco: minimum voltage v/f – Lenze 8400 StateLine User Manual

Page 769: C00978 | vfc-eco: voltage reduction, C00979 | cosine phi, C00975, C00976, C00977, C00978, C00979/2

Advertising
background image

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

769

15

Parameter reference

15.2

Parameter list | C00975

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00975

C00976

C00977

C00978

C00979

Parameter | Name:

C00975 | VFC-ECO: Vp CosPhi controller

Data type: UNSIGNED_16

Index: 23600

d

= 5C30

h

From version 10.00.00

Proportional gain of the Cos-Phi controller for energy-saving V/f characteristic control (

VFCplusEco

)

Setting range

(min. value | unit | max. value)

Lenze setting

0.000

Hz/Hz

64.000 0.500 Hz/Hz

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000

Parameter | Name:

C00976 | VFC-ECO: Ti CosPhi controller

Data type: UNSIGNED_16

Index: 23599

d

= 5C2F

h

From version 10.00.00

Reset time of the Cos-Phi controller for energy-saving V/f characteristic control (

VFCplusEco

)

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

ms

6000.0 200.0 ms

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10

Parameter | Name:

C00977 | VFC-ECO: Minimum voltage V/f

Data type: INTEGER_16

Index: 23598

d

= 5C2E

h

From version 10.00.00

Minimum voltage V/f of the Cos-Phi controller for energy-saving V/f characteristic control (

VFCplusEco

)

Setting range

(min. value | unit | max. value)

Lenze setting

20.00

%

100.00 20.00 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00978 | VFC-ECO: Voltage reduction

Data type: INTEGER_16

Index: 23597

d

= 5C2D

h

From version 10.00.00

Display of the voltage reduction with energy-saving V/f characteristic control (

VFCplusEco

)

Display range

(min. value | unit | max. value)

-1000

V

1000

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00979 | Cosine phi

Data type: INTEGER_16

Index: 23596

d

= 5C2C

h

From version 10.00.00

Display of the cosϕ setpoint and actual value with energy-saving V/f characteristic control (

VFCplusEco

)

Display range

(min. value | unit | max. value)

-1.00

1.00

Subcodes

Info

C00979/1

Cosine phi act

C00979/2

Cosine phi set

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100