Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

203

5

Motor control (MCTRL)

5.9

Parameterisable additional functions

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Settable switching frequencies

Tip!
The Lenze setting

C00018

= "2: 8 kHz var.drive-opt." is the optimal value for standard

applications.

Preventing a decrease of the switching frequency
The value must not fall below the permissible switching frequency if the motor is not approved for

the setting switching frequency or if a sinusoidal filter is connected between the output of the

inverter and the motor that is not approved for the setting switching frequency.
In order to prevent a decrease of the switching frequency, the following settings have to be made:

1. The temporary switching frequency reduction has to be activated by the setting

C00144

= "0: Off".

2. The switching frequency has to be set in

C00018

so that the value is not fallen below the

permissible switching frequency.

3. If a sinusoidal filter is available, only a drive-optimised switching frequency ("drive-opt.") is

permissible.

Example:
A sinusoidal filter is connected between the output of the inverter and the motor which only is to

be operated with a minimum switching frequency of 8 kHz.
In this case, only the following settings in

C00018

are permissible:

Selection in

C00018

1 4 kHz var./drive-optimised

21 8 kHz var./drive-opt./4 kHz min

2 8 kHz var./drive-optimised

22 16 kHz var./drive-opt./4 kHz min

3 16 kHz var./drive-optimised

23 16 kHz var./drive-opt./8 kHz min

5 2 kHz constant/drive-optimised

31 8 kHz var./min. Pv/4 kHz min

6 4 kHz constant/drive-optimised

32 16 kHz var./min. Pv/4 kHz min

7 8 kHz constant/drive-optimised

33 16 kHz var./min. Pv/8 kHz min

8 16 kHz constant/drive-optimised

Abbreviations used:

• "var.": Adaptation of the switching frequency

depending on the current

• "drive-opt.": drive-optimised modulation ("sine/delta

modulation")

• "fixed": fixed switching frequencies

• "min. Pv": additional reduction of power loss

11 4 kHz var./min. Pv
12 8 kHz var./min. Pv
13 16 kHz var./min. Pv
15 2 kHz constant/min. Pv
16 4 kHz constant/min. Pv
17 8 kHz constant/min. Pv
18 16 kHz constant/min. Pv

Selection in

C00018

7 8 kHz constant/drive-optimised
8 16 kHz constant/drive-optimised

23 16 kHz var./drive-opt./8 kHz min