background image

4

Device control (DCTRL)

4.3

Automatic restart after mains connection/fault...

96

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Case 1: No controller enable at mains connection
If the controller is not enabled at mains connection, the controller remains in the "

SwitchedOn

"

status. Only with the controller enable, the device changes to the "

OperationEnabled

" status,

independent of the set auto-start option:

Case 2: Controller enable at mains connection and "Inhibit at power-on" activated
If the controller is enabled at mains connection and the auto-start option "Inhibit at power-on" is

activated, the controller remains in the "

ReadyToSwitchOn

" status. For changing to the

"

SwitchedOn

" status, the controller enable must first be deactivated. Only when the controller is

enabled again afterwards, the status changes to "

OperationEnabled

":

Case 3: Controller enable at mains connection and "Inhibit at power-on" deactivated
If in

C00142

the autostart option "Inhibit at power-on" is deactivated (bit 0 = 0), the status first

changes from "

ReadyToSwitchOn

" to "

SwitchedOn

" and then to "

OperationEnabled

" after mains

connection with an enabled controller: