10

Oscilloscope function

10.1

Technical data

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Functional description
In the »Engineer«, you set the trigger condition and sample rate and select the variables to be

recorded via the oscilloscope user interface when an online connection to the 8400 StateLine has

been established. In this case, "variables" are the internal output signals of the function, system,

application and port blocks.
Every configuration change is transferred to the 8400 StateLine and checked. If invalid settings are

found, the oscilloscope triggers an error.
With an online connection, the measured 8400 StateLine data are transferred to the »Engineer« and

graphically represented on the oscilloscope user interface as soon as the measurement has been

completed.

10.1

Technical data

Oscilloscope function of 8400 StateLine
Number of channels

1 ... 4

Memory depth

Max. 8192 measured values, depending on the number of channels and the size of

the variables to be recorded

Data width of a channel

Max. 32 bits, corresponding to the data type of the variable to be recorded

Sample rate

1 ms or a multiple thereof

Time base

5, 10, 20, 50, 100, 200, 500 ms or 1 s

Trigger level

Corresponding to the value range of the variable to be triggered

Trigger selection

The trigger is activated if the trigger value set for the respective channel is fallen

short of or exceeded. The trigger value "must actually pass" the threshold.

Trigger delay

-100 % ... +400 %

Trigger source

Channel 1 ... 4