Parameter list | C00350

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00350

C00351

C00352

Parameter | Name:

C00350 | CAN node address

Data type: UNSIGNED_8

Index: 24225

d

= 5EA1

h

Setting of the node address via parameters

• The node address can only be parameterised if the node address "0" is set via the DIP switches.

• A change in the node address will not be effective until a CAN Reset Node is performed.

System bus "CAN on board"

Setting range

(min. value | unit | max. value)

Lenze setting

1

127 1

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00351 | CAN baud rate

Data type: UNSIGNED_8

Index: 24224

d

= 5EA0

h

Setting of the baud rate via parameters

• The baud rate can only be parameterised if the baud rate "0" is set via the DIP switches.

• A change in the baud rate will not be effective until a CAN Reset Node is performed.

System bus "CAN on board"

Selection list

(Lenze setting printed in bold)

0 500 kbps
1 250 kbps
2 125 kbps
3 50 kbps
4 1000 kbps
5 20 kbps

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00352 | CAN slave/master

Data type: UNSIGNED_8

Index: 24223

d

= 5E9F

h

The drive starts as CAN master after mains switching if a value of "1" has been entered and saved here.

System bus "CAN on board"

Selection list

(Lenze setting printed in bold)

0 Slave
1 Master

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1