7

Technology applications

7.3

TA "actuating drive speed (AC Drive Profile)"

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

7.3

TA "actuating drive speed (AC Drive Profile)"

This technology application is available from version 13.00.00!

The EtherNet/IP™ communication module supports the "AC Drive Profile".
When the controller is provided with an EtherNet/IP™ communication module and the control is to

be carried out by means of "AC Drive Profile" via EtherNet/IP™, make the following settings:

1. Set the application "1100: Actuating drive speed (AC Drive Profile)" in

C00005

.

2. Set the "40: MCI" control mode in

C00007

.

• The process data word received by the master control is then interpreted by the application

as "AC Drive Profile" control word.

• When the control is carried out via the system bus (CANopen), set the "30: CAN" control mode

instead in

C00007

.

Features

• Pre-configured control modes for terminals and bus control (with predefined process data

connection to the fieldbus)

• Free configuration of input and output signals
• adjustable offset, gain and negation of the speed setpoint
• Up to 15 fixed setpoints for speed and ramp time
• Adjustable setpoint ramp times
• Freely selectable, variable ramp shape
• Automatic holding brake control
• Quick stop (QSP) with adjustable ramp time
• Motor potentiometer function (optional)
• Process controller (optional)
• Integrated, freely available "GeneralPurpose" functions:

Analog switch, arithmetic, multiplication/division, binary delay element, binary logic, analog

comparison, D-flipflop

• Interface to the safety module (optional)
• Integration of encoder feedback

Note!

In contrast to the "actuating drive speed" standard application, this application makes

use of the nAuxSetValue_a input to determine a local speed setpoint (when NetRef=0).

For this reason, the nNAdd_a input at the

L_NSet_1

setpoint generator for determining

an additional speed setpoint is not connected in the Lenze setting.