Parameter reference

15.2

Parameter list | C00142

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00142

C00144

Parameter | Name:

C00142 | Auto-start option

Data type: UNSIGNED_8

Index: 24433

d

= 5F71

h

Starting performance of the controller after mains connection, undervoltage, loading of the Lenze setting as well as

a reset of "Trouble" or "Fault" can be parameterised individually.

Automatic restart after mains connection/fault...

Setting range

(min. hex value | max. hex value)

Lenze setting

0x00

0xFF 0x19 (decimal: 25)

Value is bit-coded: (= bit set)

Info

Bit 0  Inhibit at power-on
Bit 1  Inhibit at trouble
Bit 2  Inhibit at fault
Bit 3  Inhibit at undervoltage
Bit 4  Inhibit at Lenze setting

From version 06.00.00

Bit 5 

Reserved

Bit 6 

Reserved

Bit 7 

Reserved

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Parameter | Name:

C00144 | Switching freq. reduct. (Temp.)

Data type: UNSIGNED_8

Index: 24431

d

= 5F6F

h

Activation of the automatic switching frequency reduction if the temperature is too high
Selection list

(Lenze setting printed in bold)

Info

0 Off

Automatic switching frequency reduction deactivated

1 On

Automatic switching frequency reduction activated

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1