7 operationenabled, Operationenabled, Status – Lenze 8400 StateLine User Manual

Page 91: 4device control (dctrl)

Advertising
background image

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

91

4

Device control (DCTRL)

4.2

Device state machine and device states

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4.2.7

OperationEnabled

The drive controller is in this device status if the controller inhibit is deactivated and no error

("Trouble" or "TroubleQSP") has occurred.
If the operation is enabled and the magnetisation in case of sensorless vector control (SLVC) has

been completed, the motor follows the setpoint determined by the active application.
Depending on certain conditions, a status change takes place based on the "OperationEnabled"

device status.

Related topics:

wCANControl/wMCIControl control words

( 101)

"DRV-RDY" LED

"DRV-ERR" LED

Display in

C00137

Display in status word 1 (

C00150

)

Bit 11

Bit 10

Bit 9

Bit 8

OFF

OperationEnabled

0

1

0

1

Change condition

Changeover to the device status

Control bit "EnableOperation" of a control channel = "0"

OR terminal RFR = LOW level (controller inhibit).

SwitchedOn

Control bit "SwitchOn" of a control channel = "0".

ReadyToSwitchOn

Undervoltage in the DC bus.

Trouble

/

Fault

(depending on

C00600/1

)

Error with error response "Trouble" occurs.

Trouble

Error with error response "TroubleQSP" occurs.

TroubleQSP