Oc5: ixt overload, Oc7: motor overcurrent, Ot1: maximum torque reached – Lenze 8400 StateLine User Manual

Page 455: Xx.0119.00050, Xx.0123.00007, Xx.0123.00001, Xx.0123.00014, 9diagnostics & error management

Advertising
background image

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

455

9

Diagnostics & error management

9.9

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

oC5: Ixt overload [xx.0119.00050]

ot1: Maximum torque reached [xx.0123.00001]

oC7: Motor overcurrent [xx.0123.00007]

oU: DC bus overvoltage [xx.0123.00014]

Response (Lenze setting printed in bold)

Setting:

C00604

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The Ixt overload check has tripped.

• Operating threshold = 100 % Ixt (adjustable in

C00123

)

Possible causes:

• Wrong dimensioning of the device with regard to its

motor load.

• Load cycles are not complied with.

• Check and, if required, correct dimensioning of the

device and the motor load with regard to technical

data.

• Reduce motor load cycles (observe load cycles

according to documentation).

Response (Lenze setting printed in bold)

Setting:

C00608

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The device indicates that the maximally possible torque

at the motor shaft has been reached.

C00057

displays the current torque.

Reduce motor load.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Maximum current monitoring has tripped.

• The instantaneous value of the motor current has

exceeded the limit value set in

C00939

.

Check and, if required, correct dimensioning of the load

with regard to the installed device power.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The device has detected an overvoltage in the DC bus. To

protect the device hardware, the inverter control is

switched off.

• Depending on the configuration of the auto-start lock

function, set

C00142

so that, when this error is

tripped, the controller only restarts after the

controller inhibit has been switched.

• If this error message remains active longer than the

time set in

C00601

, a "Fault" is tripped. Otherwise, the

deactivation of the error message causes the inverter

control to be enabled again

• In case of the control types VFCplus and SLVC, the

motor voltage is approached to the voltage

setpoint alongside a ramp.

From version 15.00.00

, this voltage ramp can be set

in

C00983/2

. If the described remedies are not

possible or do not have any effect, it may be

required to increase this voltage ramp as otherwise

an overcurrent interruption may be caused. This

only happens in case of high motor power and

mass inertia so that the Lenze setting of 1 s should

be sufficient in the majority of cases.

• Reduce load in generator mode.

• Use a brake resistor.

• Use a regenerative power supply unit.

• Establish a DC-bus connection.

• Select a braking method in

C00175

which stops the

ramp function generator when reaching the brake

chopper threshold ("HlgStop").

Advertising