Current-dependent stator leakage inductance ppp(i), 5motor control (mctrl) – Lenze 8400 StateLine User Manual

Page 193

Advertising
background image

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

193

5

Motor control (MCTRL)

5.8

Sensorless control for synchronous motors (SLPSM)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.8.4.4

Current-dependent stator leakage inductance Ppp(I)

The current controller must be adjusted to the electrical characteristics of the motor stator

resistance (

C00084

) and stator leakage inductance (

C00085

). In case of modern motors, the stator

leakage inductance changes with the height of the current so that a new current controller setting

is required for each current height.
When the motor is operated with very low and very high currents (e.g. in Pick and place

applications), it is not always possible to achieve a satisfactory current controller setting for all

operating points. For this purpose, the correction of the stator leakage inductance and current

controller parameters is now possible via an adjustable saturation characteristic (17 interpolation

points).

Short overview of the relevant parameters:

Parameter

Info

Lenze setting

Value Unit

C02853/1...17

PSM: Ppp saturation characteristic (17 interpolation

points)

100 %

C02855

PSM: Imax Lss saturation characteristic

3000.0 A

C02859

PSM: Activate Ppp saturation char.

0: Off

Note!

• The saturation characteristic is not only used for the correction of the current

controller but also influences the current controller feedforward control (

C00079/1

).

• When a Lenze motor is selected from the »Engineer« motor catalogue, the

corresponding saturation characteristic is set in

C02853/1...17

and – if required – the

correction via this saturation characteristic is switched on in

C02859

.

• For third-party motors: If the current controller becomes unstable with high currents,

contact the motor manufacturer to find out whether the stator leakage inductance

changes with the current level. If required, the saturation characteristic of this motor

must be set in

C02853/1...17

and then activated in

C02859

.