Parameter reference

15.1

Structure of the parameter descriptions

596

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Scaling factor
The "scaling factor" is important for parameter access via a bus system.

Example 1: The value "654" of the parameter

C00028/1

(AIN1: input voltage) read via a bus system

must be divided by the corresponding scaling factor "100" to obtain the actual display value

"6.54 V".

[15-1] Conversion formula for read access via bus system

Example 2: In order to set the parameter

C00012

(acceleration time main setpoint) to the value

"123.45 %" via a bus system, the integer value "12345" must be transferred, i.e. the value to be set

must be multiplied by the corresponding scaling factor "100".

[15-2] Conversion formula for write access via bus system

Character length
In case of parameters of "VISIBLE_STRING" data type, the character length is given in addition. This

is also important for the parameter access via a bus system.

Signal type

Scaling factor

Resolution

Value range

Analog (scaled)

100

16 bits signed

± 199.99 %

Angular velocity

1

16 bits signed

± 32767 incr./ms

Position in [units]

10000

32 bits signed

± 214748.3647 [units]

Digital (BOOL)

1

8 bits unsigned

0 ≡ FALSE; 1 ≡ TRUE

Time

1000

16 bits unsigned

0 ... 999.000 s

Selection value

1

16 bits unsigned

0 ... 65535

Read value (via bus system)

Scaling factor

-----------------------------------------------------------------------

Indicated value (Engineer)

=

Value to be written (via bus system)

Value to be set Scaling factor

=