5

Motor control (MCTRL)

5.11

Braking operation/brake energy management

232

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Operating mode of the inverter motor brake
The ramp function generator is stopped during acceleration. The speed set in

C00987

is added to the

speed setpoint by means of a hysteresis-type 2-point DC bus voltage controller, whereby the sign of

the current actual speed is taken into account. In addition, the ramp function generator is stopped

during overvoltage.
If the DC bus voltage falls below a defined DC bus voltage potential of the hysteresis controller, the

added speed is subtracted again and the ramp function generator is activated again.
The energy is converted into heat in the motor due to alternating instances of acceleration and

deceleration as a result of this switching operation.

[5-26] Signal flow of the "Inverter motor brake" function

• In case of an asynchronous motor, the additive speed setpoint (

C00987

) should be 1 … 4 times

the slip of the machine:

[5-27] Formula for calculating the additive speed setpoint for an asynchronous motor

• In case of a synchronous motor, the additive speed setpoint (

C00987

) should be 5 … 20 % of the

rated machine speed.

DC-bus voltage

Speed setpoint for motor control

0

1

QSP

nSpeedSetValue_a

C00173
C00174
C00987

C00105

C00988

C00050

C00909/1
C00909/2

nEffSpeedSetValue_a

Œ



bLimSpeedSetVal

QSP ramp

Inverter
motor brake

p = number of pole pairs

n

Rat

= Rated speed of the motor

f

Rat

= Rated frequency of the motor

n

Sync

= Synchronous speed of the motor

C00987 [rpm]

1 ... 4 n

Sync

[rpm] n

Rated

[rpm]

(

)

=

n

Sync

[rpm]

f

Rated

Hz 60

p

--------------------------------

=