Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

201

5

Motor control (MCTRL)

5.8

Sensorless control for synchronous motors (SLPSM)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

• In

C000937/1

, the actually used maximally effective field-producing motor current is displayed.

• With switched-on and active field weakening: 0.00 A ... -x.xx A
• With sensorless control for synchronous motors (SLPSM), the injected current is displayed in

open-loop controlled operation: 0.00 A ... +x.xx A

• If neither field weakening nor open-loop controlled operation are active,e "0.00 A" is

displayed.

Example: Voltage increase in the DC bus when field weakening is switched off
(For instance by an active setting of the controller inhibit or by tripping a fault or error at high motor

speed.)

[5-20] Example: Possible DC-bus voltage > 800 V if field weakening gets lost

Note!

If a Lenze motor is used:
The controller is automatically parameterised so that field weakening operates

optimally and the maximally permissible speed is monitored.

Stop!

If an OEM motor is used:
If pulse inhibit is set in the controller, the DC bus is loaded with the voltage that

corresponds to the current speed of the machine.
Since with switched-on field weakening higher speeds can be achieved at a

correspondingly higher rotor voltage of the motor, the DC bus can be loaded to a voltage

higher than the set DC-bus voltage in case of pulse inhibit and a currently high motor

speed and even exceed the maximally permissible voltage of 800 V!
For device protection, either use a brake chopper or parameterise the motor speed

monitoring via

C00965

in such a way that only a maximum speed is possible which

would be also reachable without field weakening with a DC-bus voltage of = 800 V.

Motor speed monitoring

( 249)

Field weakening

Speed n

Motor voltage peak value

Switched off

4000 rpm

560 V

5700 rpm

800 V

6000 rpm

840 V

Switched-on

6000 rpm

560 V

• If pulse inhibit occurs at 6000 rpm and switched-on field

weakening, the DC bus is loaded to more than 800 V ().

• A speed limitation to 5700 rpm is required since this speed

causes a DC-bus voltage of 800 V if field weakening is

switched off.

n

U

4000

840 V

560 V

6000

> 800 V