Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

705

15

Parameter reference

15.2

Parameter list | C00570

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00570

C00571

C00572

Parameter | Name:

C00570 | Resp. to controller limitations

Data type: UNSIGNED_8

Index: 24005

d

= 5DC5

h

Configuration of monitoring of the motor control (group 2)
Selection list

0 No Reaction
1 Fault
5 Warning

Subcodes

Lenze setting

Info

C00570/1

0: No Reaction

Response if direct-axis current controller is limited

C00570/2

0: No Reaction

Response if cross current controller is limited

C00570/3

0: No Reaction

Response if torque setpoint is limited

• Limitation of the speed controller output, the

differential setpoint control and the additive torque

with sensorless vector control (

SLVC

).

C00570/4

0: No Reaction

Response if field controller is limited

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00571 | Resp. to wrong controller setting

Data type: UNSIGNED_8

Index: 24004

d

= 5DC4

h

From version 14.00.00

Selection list

0 No Reaction
1 Fault
2 Trouble
3 TroubleQuickStop
4 WarningLocked
5 Warning
6 Information

Subcodes

Lenze setting

Info

C00571/1

6: Information

Resp. to: Motor control does not match motor data

C00571/2

1: Fault

Resp. to a non-set speed controller

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00572 | Brake resistor overload threshold

Data type: UNSIGNED_8

Index: 24003

d

= 5DC3

h

From version 03.00.00

Adjustable threshold for monitoring the brake resistor utilisation

• The response for reaching the threshold can be selected in

C00574

.

Setting range

(min. value | unit | max. value)

Lenze setting

0

%

100 100 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1