_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

PS02: Par. set invalid [xx.0144.00002]

PS03: Par. set device invalid [xx.0144.00003]

PS04: Par. set Mci invalid [xx.0144.00004]

PS07: Par. memory module invalid [xx.0144.00007]

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The parameter set saved to the memory module is

invalid because it has not been saved completely.

• This can be due to voltage failure or caused by

removing the memory module while saving the

parameter set.

The parameter set stored in the memory module is

invalid. The reason for this can be as follows:

• Incomplete storage of the parameter set due to

voltage failure.

• The plugged-in module stems from a device with new

firmware (compare

C00099

) or from a different

device type (e.g. 8400 BaseLine).

Ensure voltage supply during the storage process and

that the module remains plugged into the slot.

Acknowledge errors via

C00002/19

or control word via

communication interface and then re-parameterise the

controller.

The error can only be removed by loading the Lenze

setting with the

C00002/1

= "1: On / start" device

command.

• In order to prevent the error, do not switch off the

voltage during the saving process.

• If the parameter set is to be transferred from one

device with a higher version to a device with a lower

version, use the "copy parameter set" function of the

keypad. Make sure that you do not use functions that

are not available in the older device.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The parameter set saved to the memory module is

incompatible to the standard device.

• An incompatibility of the parameter set is caused e.g.

when the memory module of an 8400 HighLine is

plugged into an 8400 StateLine or the parameter set

in the memory module has a higher version than

expected by the standard device.

When the memory modules are exchanged, observe the

downward compatibility:

• OK: StateLine V2.0 to StateLine V3.0

• OK: StateLine V2.0 to HighLine V2.0

• Not OK: HighLine Vx.x to StateLine Vx.x

• Not OK: StateLine V3.0 to StateLine < V3.0

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The parameter set saved to the communication module

is incompatible to the standard device.

• An incompatibility of the parameter set is caused e.g.

when the MCI module parameters in the memory

module do not match the plugged communication

module.

When the memory modules are exchanged, observe the

downward compatibility:

• OK: StateLine V2.0 to StateLine V3.0

• OK: StateLine V2.0 to HighLine V2.0

• Not OK: HighLine Vx.x to StateLine Vx.x

• Not OK: StateLine V3.0 to StateLine < V3.0

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The parameter set saved to the memory module is

invalid.

• The error occurs while loading the parameter set.

• The memory module plugged in the device lacks a

code or a code is incorrect.

Consultation with Lenze required.