9 error messages of the operating system, Error messages of the operating system, Structure of the 32-bit error number (bit coding) – Lenze 8400 StateLine User Manual

Page 444: Error, Messages of the operating system, Bit error number, 9diagnostics & error management

Advertising
background image

9

Diagnostics & error management

9.9

Error messages of the operating system

444

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.9

Error messages of the operating system

This chapter describes all error messages of the controller operating system and possible causes &

remedies.

Tip!
Each error message is also saved to the logbook in chronological order.

Logbook

( 429)

9.9.1

Structure of the 32-bit error number (bit coding)

If an error occurs in the controller, the internal fault memory saves a 32-bit value which contains the

following information:

[9-1]

Structure of the error number

• Display parameter:

C00168

From version 13.00.00:

C00162/1

additionally displays the 32-bit error number without error

type, i.e. this error number only contains the error subject area and the error ID

(bit 0 ... bit 25).

• The

LS_DriveInterface

system block shows the 32-bit error number at the outputs

wStateDetermFailNoLow (Low Word) and wStateDetermFailNoHigh (High Word).

From version 06.00.00 onwards:

If the "Use 16BitFailNo." (Bit 15 = "1") option is activated in

C00148

, the short 16-bit error number is provided by the SB

LS_DriveInterface

at the

wStateDetermFailNoLow output and the value "0" is provided at the

wStateDetermFailNoHigh output (see the following chapter).

• For the sake of legibility, the error number in the logbook and in

C00165

is displayed with the

following syntax:
[Error type].[Error subject area no.].[Error ID]

Reserved

Error type

Error subject area

Error ID

2

1

0

3

Bit

16

25

26

31

0

15

29

30

Advertising