3 autofailreset function, Autofailreset function, 9diagnostics & error management – Lenze 8400 StateLine User Manual

Page 439

Advertising
background image

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

439

9

Diagnostics & error management

9.6

Monitoring

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.6.3

AutoFailReset function

The AutoFailReset function serves to automatically reset the latching "Fault" and "TroubleQSP"

errors as well as the latching "WarningLocked" warning.
The "latching" term means that the effect on the controller remains active even after the error cause

has been removed.
To reset latching errors and warnings, the following options are available:

• Manual reset

• with device command

C00002/19

(activated by Low-High edge)

• by a Low-High edge at the bResetFail input of the

LS_DriveInterface

(the "FailReset" control

bit in the control word must be parameterised with a value of "1").

• Automatic reset

• using the AutoFailReset function.

Overview of the relevant parameters

Parameter

Info

C00184

Repetition time of the error reset processes

C00185

Time left until the next error reset process

C00186

Max. number of permissible unsuccessful error reset processes

• When the number set is reached, the response parameterised in

C00189

is executed.

C00187

Current number of unsuccessful error reset processes carried out

C00188

Configuration of the AutoFailReset function

• 0: Off

• 1: Fault + TroubleQSP

• 2: WarningLocked

• 3: All locking

C00189

Response after max. number of unsuccessful error reset processes has been

reached

Highlighted in grey = display parameter

Advertising