Xx.0131.00006, Xx.0131.00007, Xx.0127.00002 – Lenze 8400 StateLine User Manual

Page 462: Xx.0127.00015, Xx.0131.00000, 9diagnostics & error management

Advertising
background image

9

Diagnostics & error management

9.9

Error messages of the operating system

462

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

CE04: MCI communication error [xx.0127.00002]

CE0F: MCI control word [xx.0127.00015]

CE4: CAN bus off [xx.0131.00000]

CA06: CAN CRC error [xx.0131.00006]

CA07: CAN bus warning [xx.0131.00007]

Response (Lenze setting printed in bold)

Setting:

C01501/1

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Communication error with extension module in slot 1.

• Eliminate EMC interference.

• Switch off controller, correctly plug in the module,

switch on the controller again.

• Mains switching or restart of the controller,

respectively.

• Replace module/controller.

• Please contact Lenze if the problem occurs again.

Response (Lenze setting printed in bold)

Setting:

C00594/2

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Bit 14 ("SetFail") of the wMciCtrl control word of the

LS_DriveInterface

system block has been set.

Trace back signal source on the bus (e.g. PROFIBUS) that

sets bit 14 ("SetFail").

Response (Lenze setting printed in bold)

Setting:

C00592/2

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

CAN on board

: "Bus off" status

• Received too many faulty telegrams.

• Damaged cable (e.g. loose contact).

• Two nodes with the same ID.

• Check wiring and bus terminating resistor.

• Set identical baud rate for each bus node.

• Assign different IDs to nodes.

• Eliminate electrical interference (e.g. EMC).

Response (Lenze setting printed in bold)

Setting:

C00592/1

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

CAN on board

: A faulty CAN telegram has been detected.

• Check wiring and bus terminating resistor.

• Eliminate electrical interference (e.g. EMC).

Response (Lenze setting printed in bold)

Setting:

C00592/3

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

CAN on board

: Incorrect transmission or reception of

more than 96 CAN telegrams.

• The current number of incorrectly transmitted CAN

telegrams is displayed in

C00372/1

.

• The current number of incorrectly received CAN

telegrams is displayed in

C00372/2

.

• The current CAN error status is displayed in

C00345

.

• Check wiring and bus terminating resistor.

• Set identical baud rate for each bus node.

• Assign different IDs to nodes.

• Eliminate electrical interference (e.g. EMC).

Advertising