17.1.33

L_OffsetGainP_2

This FB can add an offset to an analog input signal and amplify it afterwards. Preferably to be

interconnected directly after the analog input terminals.

• The internal calculations (addition and subtraction) are carried out with 32 bits without

overflow/underflow. Division is not remainder considered.

• Offset and gain are selected via parameters.
• The value provided at the nOut_a output is internally limited to ±199.99 %.

Inputs

Outputs

Parameter

Function

Identifier

Data type

Information/possible settings

nIn_a

INT

Input signal

Identifier

Data type

Value/meaning

nOut_a

INT

Output signal

• Internal limitation to ±199.99 %

Parameter

Possible settings

Info

C00671

-100.0000

100.0000 Gain factor

• High gain factor for further

processing of smallest input

signals.

• Please observe the difference

with regard to the gain factors of

other blocks in percent

(±199.99 % ≈ 2).

• Lenze setting: 1.0000

C00697

-199.99

%

199.99 Offset

• Lenze setting: 0.00 %

/B2IIVHW*DLQ3B

Q2XWBD

“

“



Q,QBD

2IIVHW

*DLQ

&

&

nOut_a

nIn_a Offset

+

(

) Gain factor

=