4.2.4

SafeTorqueOff

Integrated safety systems with Inverter Drives 8400
Drive controller of the 8400 series can be equipped with the integrated "Safe torque off (STO)"

safety system.
The integrated safety system is applicable on machines for the protection of persons.
The drive function is still carried out by the drive controller. The safety system provides safe inputs.

If the safety system is activated, it executes control functions according to EN 60204-1 directly in

the drive controller in case of errors.

Safety state
If the drive controller is switched off by the safety system, the device changes to the

"SafeTorqueOff" status.
If the safety system deactivates the "Safe torque off (STO)" request, the device changes to the

"

ReadyToSwitchOn

" status.

"DRV-RDY" LED

"DRV-ERR" LED

Display in

C00137

Display in status word 1 (

C00150

)

Bit 11

Bit 10

Bit 9

Bit 8

OFF

SafeTorqueOff

1

0

1

0

Note!

Up to and including version 13.xx.xx the following applies:

This device status is only possible in connection with an integrated safety system and if

a power section supply is available!

From version 14.00.00 the following applies:

This device status is only possible in connection with an integrated safety system!

Detailed information on the integrated safety system can be found in the hardware

manual!
The hardware manual contains important notes on the safety system which must be

observed!
The hardware manual has been stored in electronic form on the data carrier supplied

with the 8400 drive controller.