4 evaluation of the output signal, 5 comparison function "actual value = setpoint, Evaluation of the output signal – Lenze 8400 StateLine User Manual

Page 978: Comparison function "actual value = setpoint, 17 function library

Advertising
background image

17

Function library

17.1

Function blocks

978

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

17.1.39.4 Evaluation of the output signal

After the limitation, the output signal is evaluated with the influencing factor nInfluence_a. The

evaluation is activated/suppressed along a ramp when the bEnableInfluenceRamp input is set to

TRUE. The ramp times are set with the parameters "Influence acceleration time" (

C00243

) and

"Influence deceleration time" (

C00244

).

17.1.39.5 Comparison function "Actual value = setpoint"

If setpoint and actual value are identical and there is no system deviation, the bSetEqAct status

output is set to TRUE.

• The hysteresis of the comparison function has a fixed value of 1 %.

From version 06.00.00 onwards

, the symmetrical window around the setpoint for the

comparison function can be set in

C00247

(Lenze setting: 2 %).

[17-20] Comparison function: Switching performance

[17-21] Comparison function: Example

Hysteresis (1 %, fixed value)

C00247

: Window

TRUE

FALSE

bSetEqAct

Set value

Act value

Œ 

Œ



Hysteresis (1 %, fixed value)

C00247

: Window

Act value

Set value

TRUE

FALSE

bSetEqAct

t

t

Œ





Œ

Advertising