C00420 | number of encoder increments, C00423 | dox: delay times, C00425 | encoder scanning time – Lenze 8400 StateLine User Manual

Page 680: C00420, C00425, C00420/1, C00425/1, C00423/3, C00423/4, C00423/1

Advertising
background image

15

Parameter reference

15.2

Parameter list | C00420

680

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00420

C00423

C00425

Parameter | Name:

C00420 | Number of encoder increments

Data type: UNSIGNED_16

Index: 24155

d

= 5E5B

h

Indication of the encoder constant

Encoder/feedback system

Setting range

(min. value | unit | max. value)

1

Incr./rev.

32767

Subcodes

Lenze setting

Info

C00420/1

128 incr./rev.

FreqIn12: Encoder increment

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00423 | DOx: Delay times

Data type: UNSIGNED_16

Index: 24152

d

= 5E58

h

Delay times for the digital output terminals

Digital terminals

Setting range

(min. value | unit | max. value)

0.000

s

65.000

Subcodes

Lenze setting

Info

C00423/1

0.000 s

Relay ON delay

C00423/2

0.000 s

Relay OFF delay

C00423/3

0.000 s

DO1 ON delay

C00423/4

0.000 s

DO1 OFF delay

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000

Parameter | Name:

C00425 | Encoder scanning time

Data type: UNSIGNED_8

Index: 24150

d

= 5E56

h

From version 03.00.00

Encoder sample time for the digital input terminals when configured as frequency inputs

Using DI1 and DI2 as frequency inputs

Selection list

0 1 ms
1 2 ms
2 5 ms
3 10 ms
4 20 ms
5 50 ms
6 100 ms
7 200 ms
8 500 ms
9 1000 ms

Subcodes

Lenze setting

Info

C00425/1

3: 10 ms

FreqIn12: Encoder scanning time

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1