The analog input terminals together with the analog output terminals are located on the X3 plug

connector.

Analog input terminals
The drive controller has two analog input terminals for detecting one current signal and one voltage

signal:

• Voltage signal in the ± 10 V range

The voltage signal can be e.g. an analog speed setpoint or the signal of an external sensor

(temperature, pressure, etc.).

• Current signal in the 0/+ 4 ... + 20 mA range

For open-circuit monitoring, the current signal can be evaluated with regard to "Life Zero" or

"Dead Zero":

• 0 ... 20 mA, without open-circuit monitoring
• 4 ... 20 mA, with open-circuit monitoring

Analog output terminal
The controller has an analog output terminal for outputting an analog voltage signal (O1U).

Parameterisation dialog in the »Engineer«:

Note!

To avoid undefined states, free input terminals of the controller must be assigned as

well, e.g. by applying 0 V to the terminal.

Note!

Initialisation behaviour:

• After mains switching up to the start of the application, the analog output remains

set to 0 V.

Exception handling:

• In case of a critical exception in the application (e.g. reset), the analog output is set to

0 V.