Device control (DCTRL)

4.1

Device commands (C00002/x)

78

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4.1.2

Load all parameter sets

The

C00002/6

= "1: On / start" device command reloads all parameter settings from the memory

module to the controller.

• Can only be executed if the controller is inhibited; otherwise, the feedback

C00002/6

= "6: No

access - controller inhibit" will be returned.

• All parameter changes made since the last saving of the parameter set will get lost!
• This device command has an effect on the settings of the parameters of the operating system,

application and module.

How to load the parameter settings from the memory module:

1. If the controller is enabled, it must be inhibited, e.g. by executing the "Enable/Inhibit

controller" device command "(

C00002/16

= "0: Off / ready").

2. Execute the "Load all parameter sets" device command:

C00002/6

= "1: On / start"

The loading process may take a couple of seconds. After the device command has been

called,

C00002/6

returns dynamic status information ("Work in progress 20 %"  "Work in

progress 40 %"  "Work in progress 60 %", etc.).

Notes on execution time
The execution time of this device command depends on the communication module used. If - in

addition to the device-internal time monitoring - a monitoring of the execution time is to be

implemented for this device command in a higher-level control, the monitoring time has to be 2 ...

3 times higher than the times specified in the following table:

Note!

The controller is currently provided with one data record for all parameters, i.e. every

parameter has a value. Several data records per controller are in preparation.

From version 04.00.00 onwards

, the basic function

Parameter change-over

provides a

change-over between four sets with different parameter values for up to 32 freely

selectable parameters.

( 577)

Communication module used

Typical execution time

StateLine C

HighLine C

TopLine C

Without communication module

3.5 s

3.5 s

3.5 s

PROFIBUS® or INTERBUS

3.5 s

3.5 s

3.5 s

EtherCAT®, PROFINET® or EtherNet/IP™

4.0 s

3.5 s

4.0 s

Ethernet POWERLINK

15.0 s

15.0 s

15.0 s