4 optimising the stalling behaviour, Optimising the stalling behaviour, 5motor control (mctrl) – Lenze 8400 StateLine User Manual

Page 137

Advertising
background image

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

137

5

Motor control (MCTRL)

5.4

V/f characteristic control (VFCplus)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.4.3.4

Optimising the stalling behaviour

Motor stalling due to a torque overload in the field weakening range is prevented in all

characteristic-based motor control types (VFCplus) by means of an inverter-internal stalling current

monitoring. In the field weakening range, hence at frequencies above the base frequency, it reduces

the maximum current to prevent the motor from stalling. The reduction depends on the current

field frequency, the base frequency, the DC-bus voltage and the maximum current (

C00022

).

Generally it applies that a higher field frequency causes a stronger limitation of the maximum

current.
The behaviour in the field weakening range can be adapted via the override point of field weakening

(

C00080

). This parameter serves to shift the frequency-dependent maximum current characteristic:

C00080

> 0 Hz:

• The maximum current characteristic is shifted by the entered frequency to higher field

frequencies.

• The maximally permissible current and the maximum torque increase in the field weakening

range.

• The risk of motor stalling increases.

C00080

< 0 Hz:

• The maximum current characteristic is shifted by the entered frequency to lower field

frequencies.

• The maximally permissible current and the maximum torque are reduced in the field

weakening range.

• The risk of motor stalling is reduced.

Note!

We recommend to keep the Lenze setting (0 Hz).

Advertising