1 manual dc-injection braking (dcb), 2 automatic dc-injection braking (auto-dcb), Manual dc-injection braking (dcb) – Lenze 8400 StateLine User Manual

Page 212: Automatic dc-injection braking (auto-dcb), 5motor control (mctrl)

Advertising
background image

5

Motor control (MCTRL)

5.9

Parameterisable additional functions

212

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.9.4.1

Manual DC-injection braking (DCB)

DC-injection braking can be activated manually for the two technology applications "speed

actuating drive" and "switch-off positioning" by connecting the bSetDCBrake input of the

LA_NCtrl

or

LA_SwitchPos

application block to a digital signal source (e.g. via a digital signal source bCtrl1_B3

of the

LP_CanIn1

port block).

• For HIGH-active inputs, DC-injection braking is active as long as the signal is at HIGH level.
• After the hold time (

C00107

) has expired, the controller set the pulse inhibit.

Short overview of the relevant configuration parameters:

5.9.4.2

Automatic DC-injection braking (Auto-DCB)

"Automatic DC-injection braking" (referred to in the following as "auto DCB") can be used if there is
a requirement that the drive be isolated from the supply at n

0.

Function
For understanding the auto DCB function, it is necessary to distinguish between three different

types of operation:

A. The drive has been enabled and, in the course of operation, the speed setpoint falls below the

auto DCB threshold.

• In case of V/f operation without speed feedback, a braking current (

C00036

) is injected. After

the auto DCB hold time (

C00106

) has expired, the motor is deenergised via the auto DCB

function, i.e. pulse inhibit is set.

• In case of V/f operation with speed feedback, the motor is deenergised via the auto DCB

function after the auto DCB hold time (

C00106

) has expired, i.e. pulse inhibit is set. The

braking current which can be parameterised in

C00036

does not have any effect during

operation with speed feedback.

B. When the controller is enabled, the drive is at standstill (n = 0).

If the enabled drive is to start, the speed setpoint passed via the acceleration ramp must exceed

the auto DCB threshold (

C00019

). Below this threshold, the motor will not be energised.

Parameter

Info

Lenze setting

C00701/4

LA_NCtrl

: bSetDCBrake

• "Speed actuating drive" application: Selection of

the signal source for manually activating DC-

injection braking.

Dependent on the selected

control mode

C00761/4

LA_SwitchPos

: bSetDCBrake

• "Switch-off positioning" application: Selection of

the signal source for manually activating DC-

injection braking.

Dependent on the selected

control mode

Note!

Deactivate automatic DC-injection braking when a holding brake is used!

• For this purpose, go to

C00019

and set the auto DCB threshold to "0".

• Background: Controller inhibit is already activated by the

Holding brake control

.

( 402)