Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

331

7

Technology applications

7.3

TA "actuating drive speed (AC Drive Profile)"

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

bSetQuickstop

BOOL

Enable quick stop (QSP)

• Also see device command "

Activate/deactivate quick stop

".

TRUE Activate quick stop

• Motor control is decoupled from the setpoint selection and,

within the deceleration time parameterised in

C00105

, the motor

is brought to a standstill (n

act

= 0).

• The motor is kept at a standstill during closed-loop operation.

• A pulse inhibit is set if the auto-DCB function has been activated

via

C00019

.

FALSE Deactivate quick stop

• The quick stop is deactivated if no other source for the quick stop

is active.

C00159

displays a bit code of active sources/causes for the quick

stop.

bSetDCBrake

BOOL

Manual DC-injection braking (DCB)

• Detailed information on DC-injection braking is provided in the motor control

chapter, subchapter "

DC-injection braking

".

Note!

Holding braking is not possible when this braking mode is used!

Use the basic "

Holding brake control

" function for controlling the holding brake with

a low rate of wear.

FALSE Deactivate DC-injection braking.

TRUE Activate DC-injection braking, i.e. the drive is brought to a standstill

by means of DC-injection braking.

• The braking effect stops when the rotor is at standstill.

• After the hold time (

C00107

) has expired, the controller sets the

pulse inhibit.

bRFG_Stop

BOOL

Ramp function generator: Maintain the current value of the main setpoint

integrator

• The speed, for instance, of a running ramp process is immediately kept constant

when bRFG_Stop is activated. At the same time, the acceleration/deceleration

jumps to the value "0".

• For a detailed functional description see the

L_NSet

FB.

TRUE The current value of the main setpoint integrator is held.

bRFG_0

BOOL

Ramp function generator: Lead the main setpoint integrator to "0" within the

current Ti times

In case of control via fieldbus (NetCtrl=1): If a stop is triggered via bit 0 ("Run

Forward") and bit 1 ("Run Backward") of the AC Drive Profile control word, this

signal is internally set to TRUE and thus the drive is braked to standstill.

• For a detailed functional description see the

L_NSet

FB.

TRUE The current value of the main setpoint integrator is led to "0" within

the Ti time set.

nVoltageAdd_a

INT

Additive voltage impression

• An additional setpoint for the motor voltage can be specified via this process

input.

• If there are, for instance, different loads at the motor output end, it is possible to

apply a voltage boost at the starting time.

• If the value is negative, the voltage is reduced.

• Scaling: 16384 ≡ 1000 V

Stop!

Values selected too high may cause the motor to heat up due to the resulting

current!

Identifier

Data type

Information/possible settings