C00180 | running time, C00181 | time settings, C00182 | l_nset_1: s-ramp time pt1 – Lenze 8400 StateLine User Manual

Page 644: C00184 | autofailreset repetition time, C00181/1, C00182, C00180/1, C00180/2, C00180/3, C00184

Advertising
background image

15

Parameter reference

15.2

Parameter list | C00180

644

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00180

C00181

C00182

C00184

Parameter | Name:

C00180 | Running time

Data type: UNSIGNED_32

Index: 24395

d

= 5F4B

h

Display of various running times in seconds
Display range

(min. value | unit | max. value)

0

s

2147483647

Subcodes

Info

C00180/1

Running time - control card

C00180/2

Running time - heatsink fan

C00180/3

Running time - internal fan

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00181 | Time settings

Data type: UNSIGNED_16

Index: 24394

d

= 5F4A

h

From version 06.00.00

Time for device search function (optical location)

Device search function

Setting range

(min. value | unit | max. value)

0

s

6000

Subcodes

Lenze setting

Info

C00181/1

5 s

Time - device search function

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00182 | L_NSet_1: S-ramp time PT1

Data type: INTEGER_16

Index: 24393

d

= 5F49

h

FB

L_NSet_1

: PT1 S-ramp time for the main setpoint ramp function generator

• Only effective with activated ramp rounding (

C00134

= "1").

Setting range

(min. value | unit | max. value)

Lenze setting

0.01

s

50.00 20.00 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00184 | AutoFailReset repetition time

Data type: UNSIGNED_16

Index: 24391

d

= 5F47

h

After the time set here has expired, an error message of an error that has occurred will be reset automatically if

"AutoFailReset" had been configured correspondingly in

C00188

.

AutoFailReset function

Setting range

(min. value | unit | max. value)

Lenze setting

1

s

600 3 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1