3commissioning – Lenze 8400 StateLine User Manual

Page 56

Advertising
background image

3

Commissioning

3.7

Commissioning of the "Actuating drive speed" technology application

56

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4. Adapt the application parameters:

Tip!

• Click the Signal flow button to go down one dialog level to the signal flow of the

application with further possible parameter settings. See chapter "

Basic signal flow

".

( 299)

• The preconfigured I/O connection in the selected control mode can be changed via

configuration parameters. See chapter "

User-defined terminal assignment

".

( 289)

More detailed information on the technology application:

TA "Actuating drive speed"

( 298)

Internal interfaces | application block "LA_NCtrl"

( 301)

Process data assignment for fieldbus communication

( 318)

Terminal assignment of the control modes

( 309)

Setting parameters (short overview)

( 320)

Configuration parameters

( 322)

Parameter

Lenze setting

Info

Value Unit

Accel. time - main setpoint

(

C00012

)

2.000 s

The setpoint is led via a ramp function generator with

linear characteristic. The ramp function generator

converts setpoint step-changes at the input into a ramp.

L_NSet_1 ( 952)

Decel. time - main setpoint

(

C00013

)

2.000 s

Reference speed

(

C00011

)

1500 rpm

All speed setpoint selections are provided in % and

always refer to the reference speed set in

C00011

.

The motor reference speed is indicated on the motor

nameplate.

Decel. time - quick stop

(

C00105

)

2.000 s

If quick stop is requested, motor control is decoupled

from the setpoint selection and, within the deceleration

time parameterised in

C00105

, the motor is brought to

a standstill (n

act

= 0).

Activate/deactivate quick stop ( 81)

Fixed setpoint 1

(

C00039/1

)

40.00 %

A fixed setpoint for the setpoint generator can be

activated instead of the main setpoint via the digital DI1

and DI2 inputs.

• Fixed setpoints are selected in [%] based on the

reference speed (

C00011

).

L_NSet_1 ( 952)

Fixed setpoint 2

(

C00039/2

)

60.00 %

Fixed setpoint 3

(

C00039/3

)

80.00 %

Advertising