C00700 | la_nctrl: analog connection list, Uration parameter, C00700/x – Lenze 8400 StateLine User Manual

Page 730: C00700/1, 15 parameter reference

Advertising
background image

15

Parameter reference

15.2

Parameter list | C00700

730

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00700

Parameter | Name:

C00700 | LA_NCtrl: Analog connection list

Data type: UNSIGNED_16

Index: 23875

d

= 5D43

h

Connection parameters for "Actuating drive speed" application: 16-bit inputs

• Selection of the 16 bit output signals to be connected to the 16 bit input signals

• The selection list contains all 16 bit output signals which can be assigned to the 16 bit inputs displayed by the

subcodes.

Selection list
See

selection list - analog signals

Subcodes

Lenze setting

Info

C00700/1

20005: LS_ParFix: wDriveCtrl

LA_NCtrl

: wCANDriveControl

Input for control word from CAN to device control

C00700/2

20005: LS_ParFix: wDriveCtrl

LA_NCtrl

: wMCIDriveControl

Input for control word from communication interface to

device control

C00700/3

20012: LS_ParFree_a: nC472_3_a

LA_NCtrl

: nTorqueMotLim_a

Input for maximum torque in motor mode

C00700/4

20013: LS_ParFree_a: nC472_4_a

LA_NCtrl

: nTorqueGenLim_a

Input for maximum torque in generator mode

C00700/5

0: Not connected

LA_NCtrl

: nPIDVpAdapt_a

Input for adapting the PID controller gain

C00700/6

0: Not connected

LA_NCtrl

: nPIDActValue_a

Input for actual PID controller value

C00700/7

16000: LS_AnalogInput: nIn1_a

LA_NCtrl

: nMainSetValue_a

Input for main speed setpoint

C00700/8

0: Not connected

LA_NCtrl

: nAuxSetValue_a

Input for additional speed setpoint

C00700/9

0: Not connected

LA_NCtrl

: nGPAnalogSwitchIn1_a

Input for analog switch - analog signal 1

C00700/10

0: Not connected

LA_NCtrl

: nGPAnalogSwitchIn2_a

Input for analog switch - analog signal 2

C00700/11

0: Not connected

LA_NCtrl

: nGPArithmetikIn1_a

Input for arithmetic function - analog signal 1

C00700/12

0: Not connected

LA_NCtrl

: nGPArithmetikIn2_a

Input for arithmetic function - analog signal 2

C00700/13

0: Not connected

LA_NCtrl

: nGPMulDivIn_a

Input for analog signal for multiplication/division

C00700/14

0: Not connected

LA_NCtrl

: nGPCompareIn1_a

Input for comparison operation - analog signal 1

C00700/15

0: Not connected

LA_NCtrl

: nGPCompareIn2_a

Input for comparison operation - analog signal 2

C00700/16

0: Not connected

LA_NCtrl

: nVoltageAdd_a

Input for additive voltage boost

C00700/17

0: Not connected

LA_NCtrl

: nPIDInfluence_a

Input for influence signal of PID controller correcting

variable

C00700/18

0: Not connected

LA_NCtrl

: nPIDSetValue_a

Input for PID controller setpoint

C00700/19

0: Not connected

LA_NCtrl

: nPWMAngleOffset

Input for pulse width modulation phase offset

C00700/20

0: Not connected

LA_NCtrl

: nBoost_a

Input for additional setpoint for motor voltage at speed

= 0