Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

259

5

Motor control (MCTRL)

5.14

Internal status signals | System block "LS_DeviceMonitor"

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

bWirebreakUfLinearActive

BOOL

(from version 15.00.00)

Status "V/f emergency operation due to encoder open circuit active"

• The internal change-over to "V/f emergency operation" can be suppressed by

setting bit 8 to "1" in

C02864/1

.

TRUE Due to an encoder open circuit, it is internally switched to the

encoderless V/f characteristic control in order to avoid impermissible

motor movements. This does not influence the setting in

C00006

.

Identifier

Data type

Value/meaning