3.7

Commissioning of the "Actuating drive speed" technology application

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

3.7.4

Parameterise application

The application parameters can be found on the right side of the Application parameter tab:

1. In the Control mode list field (

C00007

), select the control mode suitable for the wiring of the

terminals.

• The corresponding wiring diagram is displayed in a pop-up window if you click the

button

right to the list field.

• For a detailed description, see the chapter "

Terminal assignment of the control modes

".

( 309)

2. Optional: Use process controller.

• For this purpose, select the desired operating mode in the L_PCTRL_1: Operating mode list

field (

C00242

).

• For a detailed description see the

L_PCTRL_1

function block.

( 972)

• Go to the parameterisation dialog of the process controller via the Process controller button.

3. Optional: Use motor potentiometer.

• For this purpose, select "1: On" in the L_MPot_1: Use list field (

C00806

).

• For a detailed description see the

L_MPot_1

function block.

( 944)

• Go to the parameterisation dialog of the motor potentiometer via the Motor potentiometer

button.