Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

623

15

Parameter reference

15.2

Parameter list | C00115

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00115

C00118

C00120

Parameter | Name:

C00115 | DI1| DI2: Function

Data type: UNSIGNED_8

Index: 24460

d

= 5F8C

h

Function assignment of the digital terminals DI1 and DI2

Digital terminals

:

Function assignment

Selection list

Info

0 DI1=In1 | DI2=In2

DI1 = digital input

DI2 = digital input

1 DI1=FreqIn12 | DI2=In2

DI1 = 1-track frequency input

DI2 = digital input

2 (DI1/DI2)=FreqIn12 (2-track)

DI1 and DI2 = 2-track frequency input

3 (DI1/DI2=+-)=FreqIn12

DI1 = 1-track frequency input

DI2 = specification of direction

4 DI1=CountIn1 | DI2=In2

DI1 = counter input

DI2 = digital input

Subcodes

Lenze setting

Info

C00115/1

0: DI1=In1 | DI2=In2

Function assignment of DI1 and DI2

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00118 | DigOutX: Inversion

Data type: UNSIGNED_8

Index: 24457

d

= 5F89

h

The polarity of each digital output of the device can be inverted via this bit field.

Digital terminals

Setting range

(min. hex value | max. hex value)

Lenze setting

0x00

0xFF 0x00 (decimal: 0)

Value is bit-coded: (= bit set)

Info

Bit 0  Relay inverted

Relay inversion

Bit 1  DO1 inverted

Inversion of digital output 1

Bit 2 

Reserved

Bit 3 

Reserved

Bit 4 

Reserved

Bit 5 

Reserved

Bit 6 

Reserved

Bit 7 

Reserved

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Parameter | Name:

C00120 | Setting of motor overload (I²xt)

Data type: INTEGER_16

Index: 24455

d

= 5F87

h

Operating threshold for the "OC6: Motor overload (I²xt)" error message

• The response for reaching the threshold can be selected in

C00606

.

• The current thermal motor load is displayed in

C00066

.

Motor overload monitoring (I2xt)

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

%

250.00 100.00 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100