5.12.7

Motor phase error monitoring before operation

This function extension is available from version 11.00.00!

This extended motor phase failure monitoring can both detect a phase failure on the basis of test

signals and check for the existence of the motor.

• The "motor phase error monitoring before operation" is only directly active after controller

enable if

• an error response is set in

C00597

AND

• the motor phase error monitoring is switched on (

C2866/2

= "1: Yes").

• The following parameters show the cause of the motor phase failure:

C00561/3

: Motor phase U

C00561/4

: Motor phase V

C00561/5

: Motor phase W

Note!

The motor phase error monitoring before operation must not be connected to a rotating

or coasting machine (high compensation currents and effect of the DC injection

braking).

• In case of motor control with feedback, no motor phase error monitoring is executed

if the actual speed value is > 10 rpm.

• In case of motor control without feedback, the user must ensure that the motor phase

error monitoring will only be executed if the speed is 0.

If the motor is at quick stop and the brake is applied, no motor phase error monitoring is

executed when quick stop is deactivated (same with "0" speed and applied brake).
If the rated current of the connected motor is lower than 10 % of the rated device

current, the motor phase error monitoring can be activated although no motor phase

error has occurred. In this case, the motor phase error monitoring must be switched off

before operation (

C2866/2

= "0: No").