Electrical installation

Notes on project planning
Motor cable

6

l

112

EDS82EV903 EN 3.0

6.2.9

Motor cable

Specification

ƒ

The used motor cables must
– comply with the requirements that apply to the site of installation (e.g.

EN 60204−1, UL),

– comply with the following voltage data: EN 0.6/1 kV, UL 600 V.

ƒ

For shielded motor cables only use cables with braid made of tinned or nickel−plated
copper. Shields made of steel braid are not suitable.
– The overlap rate of the braid must be at least 70 % with an overlap angle of 90°.

ƒ

Use low−capacitance motor cables:

Power class

Capacitance per unit length

Core/core

Core/shield

0.25 ... 2.2 kW

Up to 1.5 mm

2

£75 pF/m

£ 150 pF/m

3 ... 11 kW

From 2.5 mm

2

£100 pF/m

£ 150 pF/m

15 ... 30 kW

£ 140 pF/m

£ 230 pF/m

45 ... 55 kW

£ 190 pF/m

£ 320 pF/m

75 ... 90 kW

£ 250 pF/m

£ 410 pF/m

Cable length

ƒ

The motor cable must be as short as possible for having a positive effect on the drive
behaviour.

ƒ

For group drives (several motors connected to one drive controller) the resulting
cable length l

res

is the crucial factor:

I

res

[m]

+ (l

1

) l

2

) l

3

...

) l

i

)

@ i

Ǹ

l

x

Length of the individual motor cable

l

res

Resulting length of the motor cable

i

Number of the individual motor cables

ƒ

At rated mains voltage and a switching frequency of 8 kHz and without additional
output filters, the maximum permissible length of the motor cable is as follows:
– 50 m shielded
– 100 m unshielded

)

Note!

For compliance with EMC regulations, the permissible cable lengths must be
changed.