Troubleshooting and fault elimination, Fault elimination fault messages – Lenze E82xVxxxKxxxxx User Manual

Page 457

Advertising
background image

Troubleshooting and fault elimination

Fault elimination

Fault messages

11

l

457

EDS82EV903 EN 3.0

Remedy

Cause

Fault

PC

1)

Keypad

FAn1
a

95

Fan failure
(only 8200 motec
3 ... 7.5 kW)
TRIP or warning
configurable in C0608

Fan is defective

Replace fan

FAn1

Fan is not connected

Connect fan
Check wiring

H05
a

105

Internal fault

Contact Lenze

id1
a

140

Faulty parameter
identification

Motor is not connected

Connect motor

LP1
a

32

Motor phase error
(display when C0597 =
1)

l

Failure of one/several motor phases

l

Motor current is too low

l

Check motor supply cables

l

Check V

min

boost,

l

Connect motor with a corresponding
power or adapt motor with C0599

LP1

182

Motor phase error
(Display when C0597 =
2)

LU
c

DC−bus undervoltage

Mains voltage is too low

Check mains voltage

Voltage in DC−bus connection is too
low

Check power supply module

400 V controller is connected to 240 V
mains

Connect controller to correct mains voltage

OC1
a

11

Short circuit

Short circuit

l

Search for cause of short circuit; check
motor cable

l

Check brake resistor and cable to brake
resistor

Capacitive charging current of the
motor cable is too high

Use shorter/low−capacitance motor cable

OC2
a

12

Earth fault

A motor phase has earth contact

Check motor; check motor cable

Capacitive charging current of the
motor cable is too high

Use shorter/low−capacitance motor cable

Deactivate earth−fault detection for test
purposes

OC3
a

13

Controller overload
during acceleration or
short circuit

Set acceleration time is too short
(C0012)

l

Increase acceleration time

l

Check drive dimensioning

Defective motor cable

Check wiring

Interturn fault in the motor

Check motor

OC4
a

14

Controller overload
during deceleration

Set deceleration time is too short
(C0013)

l

Increase deceleration time

l

Check dimensioning of the external brake
resistor

OC5
a

15

Controller overload
during steady−state
operation

Frequent and too long overload periods Check drive dimensioning

OC6
a

16

Motor overload
(I

2

x t overload)

Motor is thermally overloaded by e.g.

l

impermissible continuous current

l

Check drive dimensioning

l

frequent or too long acceleration
processes

l

Check setting of C0120

OH
a

50

Heatsink temperature >
+85 °C

Ambient temperature is too high

Allow controller to cool and provide for
better ventilation

OH
e

Heatsink temperature >
+80 °C

Heatsink is very dirty

Clean heatsink

OH
e

Heatsink temperature >
+80 °C

Impermissible high currents or
frequent and too long acceleration
processes

l

Check drive dimensioning

l

Check load, replace rough−running,
defective bearings, if necessary

OH3
a

53

PTC monitoring (TRIP)
(display when
C0119 = 1 or 4)

Motor too hot due to impermissible
high currents or frequent and too long
acceleration processes

Check drive dimensioning

No PTC connected

Connect PTC or switch off monitoring