Function library

Code table

10

l

409

EDS82EV903 EN 3.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0355
*

v

System bus
identifier

0

{1}

2047

l

Only for system bus function
module E82ZAFCC on the FIF
interface.

l

Display only

^ 375

1 CAN−IN1

Identifier of CAN1 with sync
control (C0360 = 1)

2 CAN−OUT1
3 CAN−IN2
4 CAN−OUT2
5 CAN−IN1

Identifier of CAN1 with event or
time control (C0360 = 0)

6 CAN−OUT1

C0356
*

v

System bus
time settings

Only for system bus function
module E82ZAFCC on the FIF
interface.

^ 375

1 Boot−up

3000 0

{1 ms}

65000 Required for CAN interconnection

without master

2 CAN−OUT2

cycle time

0

0 = event−controlled process data
transfer
> 0 = cyclical process data transfer

3 CAN−OUT1

cycle time

0

0 and C0360 = 0: event−controlled
process data transfer
> 0 and C0360 = 1: cyclical process
data transfer

4 CAN delay

20

Waiting time until start of cyclical
transmission after boot−up

C0357
*

v

System bus
monitoring
times

Only for system bus function
module E82ZAFCC on the FIF
interface.

^ 375

1 CAN−IN1 (sync)

0

0
= monitoring
inactive

{1 ms}

65000 Active if C0360 = 1

TRIP CE1 with communication
fault

2 CAN−IN2

0

TRIP CE2 with communication
fault

3 CAN−IN1 (time)

0

Active if C0360 = 0
TRIP CE3 with communication
fault

C0358
*

v

Reset node

0

0

without function

l

Only for system bus function
module E82ZAFCC on the FIF
interface.

l

Configure system bus reset
nodal point

^ 375

1

System bus reset

C0359
*

v

System bus
status

0

Operational

l

Only for system bus function
module E82ZAFCC on the FIF
interface.

l

Display only

^ 375

1

Preoperational

2

Warning

3

Bus−off

C0360
*

v

Control process
data channel
CAN1

1

0

Event or time control

Only for system bus function
module E82ZAFCC on the FIF
interface.

1

Sync control

C0370
*

v

Activate
remote
parameterisati
on via system
bus (CAN)

0

deactivated

l

Only for system bus function
module E82ZAFCC on the FIF
interface.

l

Can only be read with all other
bus function module on FIF.

^ 233

^ 244

1...63

Activates the corresponding CAN
address

1 = CAN address 1
63 = CAN address 63

255

System bus (CAN) does not exist

Display only