Function library – Lenze E82xVxxxKxxxxx User Manual

Page 339

Advertising
background image

Function library

Free interconnection of analog signals

Free configuration of analog process data output words

10

l

339

EDS82EV903 EN 3.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.
C0421
*

v
(Cont.)

Possible analog signals for C0421

^ 338

0

Output frequency
(MCTRL1−NOUT+SLIP)

24000

º 480 Hz

1

Device utilisation (MCTRL1−MOUT) at
V/f characteristic control (C0014 = 2 or
3)

16383

º Rated active inverter

current (active current/C0091)

Actual motor torque (MCTRL1−MACT)
with vector control (C0014 = 4) or
sensorless torque control (C0014 = 5)

16383

º Rated motor torque

2

Apparent motor current
(MCTRL1−IMOT)

16383

º Rated inverter current

3

DC−bus voltage (MCTRL1−DCVOLT)

16383

º 565 V DC at 400 V mains

16383

º 325 V DC at 230 V mains

4

Motor power

285

º Rated motor power

5

Motor voltage (MCTRL1−VOLT)

16383

º Rated motor voltage

6

1/output frequency (1/C0050)
(MCTRL1−1/NOUT)

195

º 0.5 ´ C0011

7

Output frequency within adjusted
limits (DCTRL1−C0010...C0011)

24000

º 480 Hz

0 5 f t C0010

24000 @ (f * C0010)

480 Hz

5 f w C0010

8

Operation with process controller
(C0238 = 0, 1):
Actual process controller value
(PCTRL1−ACT)

24000

º 480 Hz

Operation without process controller
(C0238 = 2):
Output frequency without slip
(MCTRL1−NOUT)

Advertising