Electrical installation
Standard devices in a power range from 3 ... 11 kW
Mains connection
l
133
EDS82EV903 EN 3.0
6.5.2
Mains connection
Controller of type E82xVxxxK2C (230/240 V mains)
(
Stop!
ƒ
Only connect the controller to the permitted mains voltage (
^ Technical
data). A higher mains voltage destroys the controller!
ƒ
Some controllers may only be actuated with a mains choke or mains filter.
This requirement can differ with regard to operation at rated power and
operation at an increased rated power.
ƒ
The leakage current to earth (PE) is > 3.5 mA. In accordance with
EN 61800−5−1 a fixed installation is required. The PE conductor has to be
designed double.
X1.1
3 PE AC 230/240 V
45Hz -0%...65Hz +0% 100 V -0%...264 V +0%
X1.1
PE L1
L3
+UG -UG
L2
E82EVXXXK C
2
L1
L2
L3
N
PE
0,7...0,8 Nm
6.2...7.1 lb-in
6 mm / 0.24 in
8200vec065
Fig. 6−13
Mains connection 230/240 V 3 ... 7.5 kW
X1.1/+UG,
X1.1/−UG
Supply for DC−bus operation