Function library – Lenze E82xVxxxKxxxxx User Manual
Page 416
![background image](/manuals/566070/416/background.png)
Function library
Code table
l
416
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0412
v
(Cont.)
Possible analog signal sources for
C0412
^ 328
0
Not assigned (FIXED−FREE) or selection
via keypad or parameter channel of an
AIF bus module
1
Analog input 1 (AIN1−OUT)
X3/8 (standard I/O)
X3/1U or X3/1I (application I/O)
2
Frequency input (DFIN1−OUT)
Observe C0410/24, C0425, C0426,
C0427
3
Motor potentiometer (MPOT1−OUT)
4 (A)
Analog input 2 (AIN2−OUT)
X3/2U or X3/2I
5 ... 9
Input signal is constant = 0 (FIXED0)
10
AIF input word 1 (AIF−IN.W1)
Only evaluated if C0001 = 3!
11
AIF input word 2 (AIF−IN.W2)
20
CAN−IN1.W1 or FIF−IN.W1
± 24000
º ± 480 Hz
2
14
º 100 % rated motor torque
21
CAN−IN1.W2 or FIF−IN.W2
22
CAN−IN1.W3 or FIF−IN.W3
23
CAN−IN1.W4 or FIF−IN.W4
30
CAN−IN2.W1
31
CAN−IN2.W2
32
CAN−IN2.W3
33
CAN−IN2.W4
200
Word−by−word signal assignment of
the fieldbus function module to FIF
(e.g. INTERBUS or PROFIBUS−DP)
Also see C0005
228 (A) PCTRL1−ACT
229 (A) PCTRL1−SET
230 (A) PCTRL1−OUT
231 (A) NSET1−RFG1−IN
232 (A) NSET1−NOUT
233 (A) PCTRL1−PID−OUT
234 (A) PCTRL1−NOUT
255
Not assigned (FIXED−FREE) or selection
via keypad or parameter channel of an
AIF bus module
Either NSET1−N1 or NSET1−N2
active
C0413
*
Offset − analog
inputs
−200.0
{0.1 %}
200.0 The upper limit of the setpoint
range from C0034 corresponds to
100 %
^ 298
1 AIN1−OFFSET
0.0
Setting for X3/8 or X3/1U, X3/1I
C0413/1 and C0026 are the same
2 AIN2−OFFSET
0.0
Setting for X3/2U, X3/2I
(only application I/O)
C0414
*
Gain − analog
inputs
−1500.0
{0.1 %}
1500.0
l
100.0 % = gain 1
l
Inverted setpoint selection
through negative gain and
negative offset
1 AIN1−GAIN
100.0
Setting for X3/8 or X3/1U, X3/1I
C0414/1 and C0027 are the same
2 AIN2−GAIN
100.0
Setting for X3/2U, X3/2I
(only application I/O)