Function library

Code table

10

l

416

EDS82EV903 EN 3.0

IMPORTANT

Possible settings

Code

Selection

Lenze

Name

No.

C0412

v
(Cont.)

Possible analog signal sources for
C0412

^ 328

0

Not assigned (FIXED−FREE) or selection
via keypad or parameter channel of an
AIF bus module

1

Analog input 1 (AIN1−OUT)
X3/8 (standard I/O)
X3/1U or X3/1I (application I/O)

2

Frequency input (DFIN1−OUT)

Observe C0410/24, C0425, C0426,
C0427

3

Motor potentiometer (MPOT1−OUT)

4 (A)

Analog input 2 (AIN2−OUT)
X3/2U or X3/2I

5 ... 9

Input signal is constant = 0 (FIXED0)

10

AIF input word 1 (AIF−IN.W1)

Only evaluated if C0001 = 3!

11

AIF input word 2 (AIF−IN.W2)

20

CAN−IN1.W1 or FIF−IN.W1

± 24000

º ± 480 Hz

2

14

º 100 % rated motor torque

21

CAN−IN1.W2 or FIF−IN.W2

22

CAN−IN1.W3 or FIF−IN.W3

23

CAN−IN1.W4 or FIF−IN.W4

30

CAN−IN2.W1

31

CAN−IN2.W2

32

CAN−IN2.W3

33

CAN−IN2.W4

200

Word−by−word signal assignment of
the fieldbus function module to FIF
(e.g. INTERBUS or PROFIBUS−DP)

Also see C0005

228 (A) PCTRL1−ACT
229 (A) PCTRL1−SET
230 (A) PCTRL1−OUT
231 (A) NSET1−RFG1−IN
232 (A) NSET1−NOUT
233 (A) PCTRL1−PID−OUT
234 (A) PCTRL1−NOUT
255

Not assigned (FIXED−FREE) or selection
via keypad or parameter channel of an
AIF bus module

Either NSET1−N1 or NSET1−N2
active

C0413

*

Offset − analog
inputs

−200.0

{0.1 %}

200.0 The upper limit of the setpoint

range from C0034 corresponds to
100 %

^ 298

1 AIN1−OFFSET

0.0

Setting for X3/8 or X3/1U, X3/1I
C0413/1 and C0026 are the same

2 AIN2−OFFSET

0.0

Setting for X3/2U, X3/2I
(only application I/O)

C0414

*

Gain − analog
inputs

−1500.0

{0.1 %}

1500.0

l

100.0 % = gain 1

l

Inverted setpoint selection
through negative gain and
negative offset

1 AIN1−GAIN

100.0

Setting for X3/8 or X3/1U, X3/1I
C0414/1 and C0027 are the same

2 AIN2−GAIN

100.0

Setting for X3/2U, X3/2I
(only application I/O)