Function library

Configuration of analog and digital setpoints and actual values

Setpoint changeover (hand/remote changeover)

10

l

313

EDS82EV903 EN 3.0

10.7.8

Setpoint changeover (hand/remote changeover)

Description

Changeover between the setpoints NSET1−N1 and NSET1−N2.

ƒ

With manual/remote changeover it is possible to e.g. change from remote operation
to manual operation in the event of setting or service at the drive.
– For manual operation the setpoint source for remote operation must not be

changed.

– In manual operation the setpoint is selected via potentiometer, motor

potentiometer or keypad/PC.

ƒ

Examples for setpoint changeovers:
– Bus operation

ó Keypad or PC

– Bus operation

ó analog setpoint via analog input

– Keypad or PC

ó analog setpoint via analog input

– Function Motor potentiometer"

ó analog setpoint via analog input

– Analog setpoint via analog input

ó setpoint via frequency input

– Analog input 1

ó analog input 2 (application I/O only)

)

Note!

The safety functions controller inhibit and quick stop (QSP) set in remote
operation will be reset when manual operation is being activated. Check
whether the master system reactivates these functions after a changeover.

Activation

Analog setpoint changeover via analog input

ƒ

The setpoint source for remote operation must be linked with NSET1−N1 under
C0412/1.

ƒ

The setpoint source for manual operation must be linked with NSET1−N2 under
C0412/2.

ƒ

A digital input signal must be linked with the manual/remote changeover
(DCTRL1−H/Re) under C0410/17.

ƒ

HIGH active inputs:
– Manual operation active if signal source for DCTRL1−H/Re = HIGH

Activation of "bus operation

ó keypad or PC"

1. Internally invert a digital input (X3/E5 or X3/E6) not used in the Lenze setting under

C0411.

2. Assign this input C0410/17 (DCTRL1−H/Re) to activate manual operation.

3. If the inversion of the digital input reset (C0411 = 0), remote operation will be active

again.